Jointing Tech - Rail Catalogue

Cable Lugs & Connectors Bolted Cable Lug www.jointingtech.co.uk 10 Article no. Conductor cross section area (mm2) External diameter (mm) Diameter of the mounting holes (mm) 332 595 012 50 - 240 33 Quantity of mounting holes 1 13 332-595-022 50 - 240 33 1 16 332-605-012 95 - 400 38 1 13 332-605-022 95 - 400 38 1 16 332-625-012 185 - 500 42 1 13 332-625-022 185 - 500 42 1 16 332-606-012 300 - 800 52 1 13 332-606-022 300 - 800 52 1 16 ADVANTAGES ■ Shear bolt lugs can be used independently of the conductor material, type, voltage level and current. Thanks to the special design of the bolt, optimal contact force is always achieved. The patented SICON bolt was developed without predetermined shear-off points. This means that the full load capacity of the thread is always used, thus ensuring perfect contact pressure. A friction disc on the tip of the bolt ensures that the conductor strands are not damaged. The bolt shears off smoothly when it is tightened. The remains stay in the tool and can be safely disposed of. The bolt always shears off at the top edge of the connector body. This way, there are no sharp protrusions. All edges of the connector body are rounded. SICON lugs are electrically/mechanically type-tested in accordance with IEC 61238-1 class A. Reliable connection for all conductors ■ Optimal contact force for all conductors ■ No damage to individual strands ■ Installation with standard tools ■ Ideal for all types of joints or termination ■ Wide application range SICON Bolted Cable Lug SICON Bolted Cable Lug TECHNICAL DATA ■ 72kV Rated ■ Contact technology type tested electrically and mechanically to IEC 61238-1 ■ Up to 30% increased contact force compared to conventional type terminals